Fitted isn’t the same as working: five fire safety questions to ask before 2027

In the year to March 2026, fire and rescue authorities in England carried out 50,195 fire safety audits. Only 60% ended with a satisfactory outcome recorded.

The breakdown of what went wrong matters. Maintenance was the second most frequently breached article of the Fire Safety Order, with 9,727 breaches. That is up 12% on the previous year and 52% on 2019/20. Only emergency routes and exits were breached more often.

Hereford & Worcester Fire and Rescue Service states the duty plainly: responsible persons must make sure fire safety measures are maintained in an efficient state and remain fit for purpose.

Here are five questions to put to your team and your maintainer this autumn.

1. If our alarm goes off, will anyone come?

Fire and rescue services in England attended 255,047 fire false alarms last year. Of those, 172,247 were caused by alarms or equipment operating in error, including accidental activation.

Some services now attend less. Since 1 July 2026, North Yorkshire Fire and Rescue Service has not attended automatic fire alarms at premises where people do not sleep, at any hour, unless a fire is confirmed. The service says this brings it into line with others regionally and nationally. Dorset & Wiltshire stopped attending automatic alarms at low-risk commercial premises on 1 April 2024.

In those areas, a 999 call or other confirmation of fire is what brings a response. Dorset & Wiltshire also points out that investigating the cause of an automatic alarm is the premises’ responsibility, not the fire service’s. BS 5839-1:2025 says the same: the user should arrange for every false alarm to be investigated.

Ask: Who on site confirms a fire and calls 999, on every shift? And who investigates each false alarm?

2. How does our alarm signal leave the building?

The UK’s analogue telephone network (PSTN) is being permanently switched off by 31 January 2027. Hereford & Worcester Fire and Rescue Service warns about fire alarms that signal to an alarm receiving centre (ARC) over lines not upgraded in time. Activations may not be transmitted correctly, and fault monitoring could be affected.
BS 5839-1:2025 now sets transmission timings.

For a Category L system:

  • A fire signal should reach the ARC within 90 seconds.
  • A failure of all transmission paths should show at the ARC and the control panel within 3 minutes.

The signals sent to the ARC should also be checked at every service visit, including each type of signal where more than one is sent.

Ask: Will our signalling path still exist after 31 January 2027, and can we see the result of the last ARC signal check?

3. Which edition of BS 5839-1 was our system built to?

BS 5839-1:2025 replaced the 2017 edition on 30 April 2025. It is a code of practice, so variations from its recommendations are allowed, but the new edition tightens how they are handled:

  • All agreed variations should now be recorded in the system logbook.
  • Some departures are no longer regarded as acceptable at all, such as having no zone plan where a storey has more than one zone.

New recommendations are not automatically retrospective. The Fire Industry Association notes that heat detectors are no longer permitted in rooms where people sleep. Existing systems don’t have to change unless they are having new work. Extensions should meet the current edition, even where the rest of the system doesn’t.

The 2025 edition also adds a clause on remote services and cyber security for connected fire panels.

Ask: Which edition was our system designed to, and are all its variations recorded in the logbook?

4. Is our fire risk assessment written in full, and who wrote it?

Since 1 October 2023, amendments made by section 156 of the Building Safety Act 2022 have applied to every responsible person, regardless of the size of the business. You must record:

  • your fire risk assessment, in full;
  • your fire safety arrangements;
  • the name of any person or organisation who carried out the assessment.

Breaches of Article 11, which covers fire safety arrangements, rose 25% last year to 5,240.

The next change concerns the assessors. Recommendation 26 of the Grenfell Tower Inquiry’s Phase 2 report called for mandatory accreditation of fire risk assessors. The government consulted on it between 26 March and 18 June 2026. It says it will legislate to require assessors’ competence to be independently verified by a UKAS-accredited certification body. Its response to the consultation is expected between October and December 2026. That requirement is not law yet.

Ask: When was our assessment last reviewed, who carried it out, and does it reflect how we use the building today?

5. Are our escape routes usable, and will the walls around them hold?

Emergency routes and exits were the most frequently breached article of the Fire Safety Order last year: 11,286 breaches, up 9.3%.

Routes, exits and fire doors can be checked on foot. Compartmentation can’t. It is the fire-resisting walls, floors and ceilings that hold fire and smoke back from those routes, and the cavity barriers that stop fire spreading through hidden voids.

On recent fire strategy and fire risk assessment visits across a large multi-site UK estate, our Life Safety Systems team recommended compartmentation surveys and cavity barrier surveys after finding failings in these passive measures. Some had been overlooked, or not checked for some time.

Ask: When did someone last walk our escape routes and check every exit and fire door? And when was our compartmentation last surveyed, including above ceilings and in voids?

The five questions

1. If our alarm activates, who confirms a fire and calls 999, and who investigates false alarms?

2. Will our alarm signalling still work after 31 January 2027?

3. Which edition of BS 5839-1 is our system built to, and are its variations recorded?

4. Is our fire risk assessment written in full, current, and carried out by someone competent?

5. Are our escape routes usable today, and when was our compartmentation last surveyed?

 

If you can’t answer one of them, talk to Evolution’s Life Safety Systems team